Panel power supply

VE service type PZP 1.1

Checking or manual control of 4-20 mA current circuits

Operating modes

Mode A (automatic)

current passes through a device into a controlled device unchanged. The magnitude of the current is shown by a number of lit LEDs in %.

Mode M (manual)

Input current loop is interrupted, the current on the output has the magnitude of a series of lit LEDs in%. Using buttons, the size of this current can be more or less changed. Switching back to the A (automatic) mode, you can either press M/A or remotely by applying voltage (connection) on AUT terminals.

Technical parameters

  • Current range: 4 - 20mA
  • Internal power supply: 4 - 20mA (max. 25 mA)
  • Display: 0 -100% in 10%
  • Switching to AUT: external voltage 12-30V or switching contact
  • Load resistance: max. 240 R
  • Through resistance: 56 R
  • Voltage: 230 V / 50-60 Hz
  • Power input: max. 2VA
  • Protection: IP54 (front), IP20 others
  • dimensions (w x h x d): 48 x 48 x 90 (mm)
  • Weight: 170 g
  • Operating conditions (ambient temperature): 10 - 35 °C
  • Relative humidity: 30 - 70 %
  • Storage conditions (temperature): -10 - +40 ℃
  • The unit can be supplied with galvanic isolation between input and output